Hydrogen fire in a sulphur recovery unit of a refinery
Three workers were working in the sulphur recovery unit (SRU), trying to restore the hydrogen flow. The workers were trying to isolate the cause of a flow problem: hydrogen was entering the regulators at 200 psi (14 bar), but the pressure was dropping to 18 to 20 psi (approximately 1. 3 bar) after the passed through the various components of the unit. They closed a valve preceding the regulators and vented the bleed manifold before removing a flange located beyond the valve. One of the worker then re-opened the closed valve to check the flow. A hiss was heard, followed by a pop, and the area became engulfed in flames. The three workers suffered burns .
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE was the wrong operation during the search for a flow problem. Nothing is known on the main problem which triggered the action. The ROOT CAUSE could be identified in a combination of two FACTORS: (1) the intervention of the repairing team appeared characterised by improvisation, in absence of a good script (procedures), and therefore somebody made some errors. (2) it is very probable that the team did not have a full understanding of the pressure control system they were working on, and this call for a better technical knowledge and safety awareness, to be ensure by the management by effective training.