Hydrogen explosion from a truck
An open backed truck was delivering various to various sites industrial gases, among which hydrogen. At the site of the explosion a rack of argon gas bottles was being delivered to a laboratory in the building adjacent to the truck. The small lifting arm at the back of the truck was being used to offload the argon gas bottles when the operator (truck driver) heard a hissing sound. The operator stopped what he was doing and went to investigate the source of the sound at which point an explosion took place. The official accident investigation is not available, but the scientific article referred among the sources (Venetsanos et al. ) report that according to that report the release was the result of two broken connections between pressure vessels adjacent to 6 mm diameter T-connection outlets from the cylinders. Shut-off valves were not used to secure the individual cylinders in the rack. The hydrogen ignited and exploded with an over-pressure of 5 kPa experienced at a distance of 90 m from the centre of the explosion. The official investigation estimated that an over-pressure of 5 kPa (50 mbar) was experienced at a distance of 90m from the centre of the explosion, based on the damage caused by the explosion.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING cause was the failure of connections between cylinders. The ROOT CAUSE is unknown, but a contributing cause appears to be a design shortcoming (material choice, safety design not considering individual shut-off valves).