Skip to main content

Hydrogen explosion in a rocket fuels laboratory (826)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen explosion in a rocket fuels laboratory

In a laboratory, tests with hydrogen as aerospace rocket propellants were carried out. One of the experiments consisted in the generation of a vertical jet (turbulent regime) to determine the sound levels emitted by jets of H2 gas. It consisted in the intentional venting of 1000 kg of hydrogen at 23 MPa within 30 s. The discharge flow was uniformely increased upt to 55 kg/s, maintained for 10 seconds and then reduced to zero, After 26 s, while decreasing the flow, the hydrogen unintentionally ignited. A fireball was formed followed immediately by an explosion. The Vapour Cloud explosion VCE caused damage to structures of the surrounding buildings (walls, doors, roofs). The over-pressure was estimated at 0. 035 bar to 45 m. The burning gas cloud of approx. 9 m diameter and 45 m height cotnaining 9 to 10 kg of hydrogen. According to the ARIA report, the cause of the ignition appeared to be due to static electricity and or a spark of mechanical origin. [Note of HIAD Validator: on the quantity of hydrogen involved in the explosion, the sources diverge (see reference): for ARIA it was 90 kg, for PRESLHY it was 9 kg, for Lee it was 10 kg, corresponding to a TNT equivalent of 8%. Here it is assumed that the value provided by ARIA was a typo]
Event Date
January 9, 1964
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the unplanned ignition of a hydrogen flow during an experiment. IGNITION was probably due to static electricity and / or a spark of mechanical origin. The ROOT CAUSE was proably a shortcoming in the design and execution of the experiment, due to the presence of unanted ignition sources.
Facility Information
Application Type
Application
Laboratory / R&D
Specific Application Supply Chain Stage
Components Involved
laboratory, vertical jet experiment
Storage/Process Medium
Location Type
Location description
For abackground information regarding this NASA project, see Wikipedia page https://en. wikipedia. org/wiki/Project_Rover#CITEREFFinseth1991 (accessed November 2025)
Operational Condition
Pre-event Summary
According to the Wikipedia page dedicated to the testing facility, previous accidents with hydrogen had already taken place in the year 1960-64. This is not surprising, because the laboratory was one of the first in the world studying hydrogen properties.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

VCE (mainly negative overpressure) causes damage to structures (walls, doors, roofs) of buildings. The overpressure is estimated to be 0. 035bar to 45 m and the amount of H2 involved in the explosion is 90 kg (othe source says 10 kg). Explosion was heard 3. 2 km away. TNT equivalent of 8%.

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Release Duration (s)
23
Release Rate (kg/s)
55.00
Release Amount (kg)
90.00
Ignition Source
Ignition Delay (s)
23
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Prof. J. Lee presentation at 1st European Summer School on Hydrogen Safety (ESSH) available at the HySafe project site http://www. hysafe. org/science/eAcademy/php/1stesshsprogramme. php (see slides from 13 to 15, accessed October 2020)

Gummer & Hawksworth, literature review on Spontaneous ignition of hydrogen , HSE (2008) https://webarchive. nationalarchives. gov. uk/ukgwa/20241207091242/https://www. hse. gov. uk/research/rrhtm/rr615. htm (accessed November 2025)

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/10095_en/?lang=en(accessed October 2020)