Hydrogen explosion at a refuelling station
This incident occurred at a hydrogen refuelling station with on-site hydrogen production based on reforming of city gas and natural gas. The part affected was a coil in the heat exchanger belonging to one of the two hydrogen production units. The unit was shut down and under preventive maintenance and was resuming operation. The coil broke at a weld, releasing hydrogen, which flowed into the exhaust vent and ignited due to static electricity, causing an explosion at the exit of the vent pipe. The investigation revealed that the coil broke at a weld located at a bending point, due to local concentration of stress and fatigue. These factors were mainly due to the geometry of the coil, a weld of difficult manufacturing, and the fact that during pressure transients, water condensation occurred, increasing the local stresses.

The INITIAL CAUSE was the failure of a subcomponent due to concentrated and repeated high stresses. The ROOT CAUSE was shortcoming in design, which did not considered the effect of operation transients and the possibility of local condensation of water.