Hose rupture at a HRS
A dispenser hose failed at a hydrogen refuelling station. It ruptured with a sidewall burst, approximately 30 cm from the crimped end fitting. The hose had experienced a total of aproximately 300 filling cycles. The rupture occurred while it was temporarily connected to a gas booster, after 1-2 hours of service at 75 MPa. There were no tight bends in the hose during its final service application and no vibration present in the assembly. The post-rupture examination revealed that the hose contained three distinct kinks, or bent areas, within the immediate area of the failure. However, the burst area did not show any obvious signs of previous damage or flaws. Some strands of the metal braiding exhibited corrosion attack, as well as gouge-type mechanical damage, but no fatigue characteristics or discontinuities were noted on the failed strands that were examined. [H2TOOLS]