Fire on a hydrogen pipe of a refinery
This incident occurred at a refinery, on a pipe transporting hydrogen at 24 bar placed at 6 m above ground. A 15 cm long hydrogen flame was detected at an anti-leak system temporarily installed on the pipe to prevent a leak on a damaged valve. This temporary system had been installed a year earlier, to allow continuation of the operation, avoiding the need of a shut-down of the whole unit. The crisis unit and the emergency plan were activated. Internal response teams set up a safety perimeter. Units were put on standby to isolate and decompress the section. The leak was stopped after 3 hours. The excess hydrogen produced by the unit was sent to the flare network pending repairs. Leak tests were performed on the isolation valves of the line section. The temporary system was removed, and the leaking valve, which was not required for operation, was removed. The emergency plan 8 hours after the start of the emergency.