Fire on a hydrogen pipe of a refinery (1192)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on a hydrogen pipe of a refinery

This incident occurred at a refinery, on a pipe transporting hydrogen at 24 bar placed at 6 m above ground. A 15 cm long hydrogen flame was detected at an anti-leak system temporarily installed on the pipe to prevent a leak on a damaged valve. This temporary system had been installed a year earlier, to allow continuation of the operation, avoiding the need of a shut-down of the whole unit. The crisis unit and the emergency plan were activated. Internal response teams set up a safety perimeter. Units were put on standby to isolate and decompress the section. The leak was stopped after 3 hours. The excess hydrogen produced by the unit was sent to the flare network pending repairs. Leak tests were performed on the isolation valves of the line section. The temporary system was removed, and the leaking valve, which was not required for operation, was removed. The emergency plan 8 hours after the start of the emergency.

Event Date
September 10, 2024
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Facility Information
Application Type
Application
Unknown
Specific Application Supply Chain Stage
Components Involved

valve, pipe

Storage/Process Medium
Actual Pressure
2
Design Pressure
2
Location Type
Operational Condition
Pre-event Summary

The temporary system had been installed a year earlier. This so-called “leak-in-operating” device is a temporary device installed on a leak in an industrial facility, such as a pipe or valve, to allow for a safer repair, often avoiding a shutdown of the facility. These systems are subject to strict procedures, including risk analysis and equipment monitoring, and must be replaced with a permanent repair during the first scheduled shutdown, or at the latest by the regulatory deadline.

Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

0

Property Loss (offsite)

0

Lessons Learned

The event description is mainly based on local news information, and lack of the required technical details to extract a specific lesson learnt. The consequences have been rather limited, the emergency actions were effective, nobody was injured and there was no impact outside the fence. Nevertheless, it is still possible to formulate the following reflection: (1) At the origin of the series of event there was a leaking. A temporary leak-in-operating had been installed to avoid the immediate shut-down of the industrial process. (2) The incident occurred a year after the device had been installed. (3) The leak-in-operating solution is a temporary solution, which must be replaced with a permanent repair during the first scheduled shutdown. (4) Clearly, the design and/or the installation of this device was not enough to guarantee leak-free operation for such a long time.

Event Nature
Emergency Action

The crisis unit and the emergency plan were activated. Internal response teams set up a safety perimeter. It was necessary to install a scaffolding to reach the leaking location. Units were put on standby to isolate and decompress the section. The leak was stopped after 3 hours. The excess hydrogen produced by the unit was sent to the flare network pending repairs. Leak tests were performed on the isolation valves of the line section. The temporary system was removed, and the leaking valve, which was not required for operation, was removed. The emergency plan 8 hours after the start of the emergency.

Release Type
Release Substance
H2
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Event no. 62767 of the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/62767/ (accessed December 2024)

News of L'Echo https://actu. fr/pays-de-la-loire/donges_44052/une-fuite-dhydrogene-enflammee-a-la-raffinerie-totalenergies-de-donges_61587451. html#:~:text=Donges-,Une%20fuite%20d'hydrog%C3%A8ne%20%C2%AB%20enflamm%C3%A9e%20%C2%BB%20%C3%A0%20la%20raffinerie%20Total%C3%89nergies,a%20pas%20eu%20de%20bless%C3%A9s. &text=Copiez/Collez%20le%20Lien%20Copi%C3%A9%20! (accessed Septeber 2025)

News of Ouest France https://www. ouest-france. fr/pays-de-la-loire/donges-44480/fuite-dhydrogene-fin-de-lincident-a-la-raffinerie-totalenergies-de-donges-d645ccca-7013-11ef-bf8c-5742d8eb2cd3