Fire during hydrogen transfer between stationary storage and trailer
The ignition of a hydrogen leak occurred at a semitrailer connected to a pressure reducing station, while waiting a transfer. The alert was given by personnel of the company cafeteria located nearby. The external rescue crews arriving at the site 15 min later reported a very sizeable gas leak ignited at the rear of the semitrailer, near the vertical bottle storage area. The red-white heat at the end of the semitrailer platform raised fears over deterioration of the bottle valves. Moreover, the pressure reducing station to which the semitrailer was connected (the former station was being used as an emergency centre) had been the origin of many ignited leaks. Four other semitrailers were positioned in the transfer station connected to a second pressure reducing station (new one): one was connected and in a wait mode, one not connected, and two connected and being serviced. The definitive elimination of the damaged pressure reducing station (emergency centre) would be used to resume distribution network operations the next day. All of the semitrailer connection studs could be refurbished in a way that offsets the risk of destruction by heat.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE an unspecified hydrogen leak. The IGNITION SOURCE is supposed having been lightning. The pressure reducing station to which the semitrailer was connected (the former station was being used as an emergency centre) had been the origin of many ignited leaks.