Fire during hydrogen transfer between stationary storage and trailer (763)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire during hydrogen transfer between stationary storage and trailer

The ignition of a hydrogen leak occurred at a semitrailer connected to a pressure reducing station, while waiting a transfer. The alert was given by personnel of the company cafeteria located nearby. The external rescue crews arriving at the site 15 min later reported a very sizeable gas leak ignited at the rear of the semitrailer, near the vertical bottle storage area. The red-white heat at the end of the semitrailer platform raised fears over deterioration of the bottle valves. Moreover, the pressure reducing station to which the semitrailer was connected (the former station was being used as an emergency centre) had been the origin of many ignited leaks. Four other semitrailers were positioned in the transfer station connected to a second pressure reducing station (new one): one was connected and in a wait mode, one not connected, and two connected and being serviced. The definitive elimination of the damaged pressure reducing station (emergency centre) would be used to resume distribution network operations the next day. All of the semitrailer connection studs could be refurbished in a way that offsets the risk of destruction by heat.
Event Date
June 13, 1988
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE an unspecified hydrogen leak. The IGNITION SOURCE is supposed having been lightning. The pressure reducing station to which the semitrailer was connected (the former station was being used as an emergency centre) had been the origin of many ignited leaks.
Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved
tube, hose, pressure reducing station,
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
Hydrogen leakages and ignition had already previously occurred.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

The definitive elimination of the damaged pressure reducing station (emergency centre) was used to resume distribution network operations the next day. All of the semitrailer connection studs could be refurbished in a way that offsets the risk of destruction by heat.

Event Nature
Emergency Action
The alert was sounded by personnel of the company cafeteria located nearby. The external rescue crews arriving at the site 15 min later reported a very sizeable gas leak ignited at the rear of the semitrailer, near the vertical bottle storage area. The excess red-white heat at the end of the semitrailer platform raised fears over deterioration of the bottle valves. The first measures undertaken consisted of cooling, by flooding all bottle heads on the leaking semitrailer, and removing the other semitrailers. In addition, the hydrogen production equipment was shut off in order to isolate the distribution network. Two hours later, with the pressure inside bottles on the damaged semitrailers having dropped, rescue personnel could get close enough to close the valves. Lightning would have caused the accident.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

ARIA data base event no. 343