Fire on a compressor at a hydro-tretement unit
A fire developed at a recycle gas compressor of a refinery. During recommissioning, the compressor, belonging to a hydro-treatement unit, was overpressurised. The cylinder head was blown off, resulting in an explosive decompression and fire. It was found that the discharge valve was installed in the wrong direction.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
Investigations into the accident showed that the INITIATING CAUSE was the installation of one of the discharge valves in the reverse direction. This results in the build up of pressure within the cylinder. The criticality of the task to replace the valve had not been understood or reflected in procedures. Although the compressor was purchased according to the API 618 standard, which requires a design that prevent valves from being installed in the wrong direction, the equipment did not meet specification. The ROOT CAUSES were shortcoming in maintenance procedure and in quality assurance when dealing with contractors/manufacturers.