Skip to main content

Fire on a compressor at a hydro-tretement unit (110)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on a compressor at a hydro-tretement unit

A fire developed at a recycle gas compressor of a refinery. During recommissioning, the compressor, belonging to a hydro-treatement unit, was overpressurised. The cylinder head was blown off, resulting in an explosive decompression and fire. It was found that the discharge valve was installed in the wrong direction.
Event Date
October 1, 1995
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
Investigations into the accident showed that the INITIATING CAUSE was the installation of one of the discharge valves in the reverse direction. This results in the build up of pressure within the cylinder. The criticality of the task to replace the valve had not been understood or reflected in procedures. Although the compressor was purchased according to the API 618 standard, which requires a design that prevent valves from being installed in the wrong direction, the equipment did not meet specification. The ROOT CAUSES were shortcoming in maintenance procedure and in quality assurance when dealing with contractors/manufacturers.
Facility Information
Application Type
Application
hydro-refiner
Specific Application Supply Chain Stage
Components Involved
valve, compressor head, compressor,
Storage/Process Medium
Location Type
Location description
The ICHEME report used the term Hydrofiner: this is an industrial unit, primarily in oil refineries, that uses hydrogen and catalysts to remove impurities (sulphur, nitrogen, aromatics) from petroleum fractions, improving fuel quality (like gasoline, diesel, jet fuels). The more generic term is catalytic hydrotreating process to "clean" oil products, making them cleaner burning and more valuable. The report does not specify the composition of the process gas, but it is known the the recycled gas consists mainly of hydrogen with traces of H2S.
Operational Condition
Consequences
Number of Injured Persons
7
Number of Fatalities
0
Currency
Property Loss (onsite)
900000
Post-event Summary

Production losses and repair costs were estimated at $500,000 (1995) (£318,300) and $400,000 (£254,600) (1995), respectively.

Lessons Learned

The lesson learnt from this event was that the company had to review and improve the quality control and assurance of the products obtained from third parties. This review must consider all components playing a critical role in guaranteeing safety of the plant.

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event nr 8373 of the UK database ICHEME ICHEME database is no longer available, but data can be download as PDF for free. https://www. icheme. org/knowledge/safety-centre/resources/accident-data/ (accessed October 2020)