Fire from a CHG2 trailer during filling
The incident occurred at the site of a gas production company. During the filling of a compressed hydrogen trailer, an end plug thermal pressure relief device (TPRD) had an unplanned activation. The released hydrogen vented through a leak in the vent manifold of the TPRD venting system, which appeared to be improperly assembled. The ignition of the hydrogen caused significant damage to the trailer and damage to the another trailer which was being filled alongside the affected trailer.
Event Date
August 12, 2023
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE was the unexpected activation of a thermal pressure relief device The ROOT CAUSES were a material failure combined with the wrongly installation of the venting system manifold.