Fire from a CGH2 trailer (382)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire from a CGH2 trailer

Near the end of the process of filling a gaseous hydrogen tube trailer at a liquid hydrogen trans-filling station, a safety pressure-relief device (PRD) rupture disc on one of the tube trailers ten tubes burst and vented hydrogen gas. The PRD vent tube directed gas to the top of the trailer where the hydrogen vented and ignited, blowing a flame straight up in the air. The operator filling the tube trailer heard a loud explosion from the sudden release of hydrogen gas and saw flames immediately. The operator closed the main fill valve on the tube trailer, stopping the hydrogen fill; however, the ten cylinders on the tube trailer were almost full (2500 psig/173 bar). The tube trailer involved in this incident was one of two tube trailers being filled simultaneously and was second in a line up of five tube trailers parked adjacent to one another at this location. Source: H2TOOLS
Event Date
January 2, 2009
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING CAUSE was the premature opening of a rupture disc The PRD rupture disc designed for 3500 psig (241 bar) failed at about 1000 psig (69 bar) below rated pressure. According to H2TOOLS, follow-up examination of the rupture disc lot by the manufacturer found that all of the lot conformed to specification. Therefore also t he ROOT CAUSE can only be attributed to a material failure.
Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved
Burst disc, PRV
Storage/Process Medium
Actual Pressure
17
Design Pressure
20
Location Type
Operational Condition
Pre-event Summary
According to H2TOOLS, the trailer involved in this incident was at its first refilling after requalification, and all the PRDs had just been replaced.
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Post-event Summary

Emergency responders were dispatched to the scene. The facility deluge system was turned on. This system covers the trailer fill aisle with water and includes nozzles at the rear of the trailer and a fire cannon directed to the front. When the emergency responders arrived, they immediately began spraying the adjacent trailers to ensure that they stayed cool. The HazMat crews closed the 10 individual tube fill isolation valves located at the rear of the tube trailer and extinguished the fire. Total time to control the incident was less than 10 minutes and there was no property damage from this event.

Lessons Learned
1. Specific response drills/exercises need to be conducted yearly. In this case, all safety systems worked as they should and outside emergency responders were not needed. 2. Performing other tasks while filling hydrogen tube trailers, such as mechanic work, should be avoided. Most premature failures of hydrogen tube trailer PRD burst discs occur during the fill process. 3. Grounding, as was done in the incident, should always be done during hydrogen filling. However, even when the fill vessel is grounded, it is not unusual for a hydrogen release to immediately ignite. 4. The facility safety deluge water system should be checked periodically for coverage. In this case, a water cannon was a little off target from the last time it was operated and has now be repositioned and stabilized to ensure that it does not move in the future. 5. Emergency responders assumed that adjacent tube trailers were heating up from single-cylinder vent flare as a 300°F (149°C) reading was obtained with a thermal device. This slightly delayed the closing of the cylinder isolation valves on the tube trailer. After-incident investigation found no paint discoloured or burnt, so the temperature taken by the emergency responders was likely near the flaming vent discharge point. 6. Securing hydrogen fill valve(s) at the back of the tube trailer was not dependent on the temperature at the vent stack, as this area was covered by deluge nozzles and located 40 feet (12. 2 meters) away from the vent stack. 7. Media involvement and resulting speculation can portray a situation as being much worse than it actually is.
Event Nature
Emergency Action
Emergency responders were dispatched to the scene. The facility deluge system was turned on. This system covers the trailer fill aisle with water and includes nozzles at the rear of the trailer and a fire cannon directed to the front. When the emergency responders arrived, they immediately began spraying the adjacent trailers to ensure that they stayed cool. The HazMat crews closed the 10 individual tube fill isolation valves located at the rear of the tube trailer and extinguished the fire. Total time to control the incident was less than 10 minutes and there was no property damage from this event.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Events exchanged with the database H2TOOLS https://h2tools. org/lessons/hydrogen-tube-trailer-burst-disc-ruptures-prematurely-while-filling