Fire from a CGH2 trailer (382)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Fire from a CGH2 trailer
Near the end of the process of filling a gaseous hydrogen tube trailer at a liquid hydrogen trans-filling station, a safety pressure-relief device (PRD) rupture disc on one of the tube trailers ten tubes burst and vented hydrogen gas. The PRD vent tube directed gas to the top of the trailer where the hydrogen vented and ignited, blowing a flame straight up in the air. The operator filling the tube trailer heard a loud explosion from the sudden release of hydrogen gas and saw flames immediately. The operator closed the main fill valve on the tube trailer, stopping the hydrogen fill; however, the ten cylinders on the tube trailer were almost full (2500 psig/173 bar). The tube trailer involved in this incident was one of two tube trailers being filled simultaneously and was second in a line up of five tube trailers parked adjacent to one another at this location. Source: H2TOOLS
INITIATING CAUSE was the premature opening of a rupture disc The PRD rupture disc designed for 3500 psig (241 bar) failed at about 1000 psig (69 bar) below rated pressure. According to H2TOOLS, follow-up examination of the rupture disc lot by the manufacturer found that all of the lot conformed to specification. Therefore also t he ROOT CAUSE can only be attributed to a material failure.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.