Fire from a CGH2 cylinders truck (287)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire from a CGH2 cylinders truck

A truck loaded with 22 hydrogen cylinders pallets (370 litres each) was traveling on a national highway. While stopped at a traffic light, it was rear-ended by a large truck which damaged the piping and valves of the pallets, causing hydrogen gas to eject and ignite. Both drivers were killed, and two passers-by were injured. In addition, nearby shops and houses were set on fire. The truck driver had fallen asleep while driving.

Event Date
May 25, 1972
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the failure of a conventional component (tyre) . The ROOT CAUSE was probably the lack of effective protection of the pressure and flow control system of the cylinders, which were not designed for impacts coming collisions from the vehicles.

Facility Information
Application
CGH2 cylinders truck
Specific Application Supply Chain Stage
Components Involved

piping, valves

Storage/Process Medium
Storage/Process Quantity
118
Location Type
Operational Condition
Pre-event Summary

22 pallets of 370 l each gives a total water capacity of 8 m3. Assuming a pressure of 200 bar, it provide estimation of the transported quantity of ca. 120 kg

Consequences
Number of Injured Persons
2
Number of Fatalities
2
Environmental Damage
0
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): https://www. khk. or. jp/public_information/incident_investigation/hpg_incident/incident_db. html (accessed May 2025)