Fire caused by tube trailer roll-over
A tube trailer was returning to the basis after having delivered compressed hydrogen to a customer site. The vehicle was operated by two drivers taking turns in driving. While traveling on a highway, a light four-wheeled vehicle overtook the vehicle from the rear on the right and entered the path of the container transport vehicle, so the tube trailer had to brake and perform a sudden change of direction to avoid the other vehicle. It collided with the shoulder of the embankment, rolling-over and crashing into the riverbed. The mechanical impact with the ground shock caused the blind flange of the tubes manifold to break, releasing hydrogen which first exploded and then produced a fire , which burned most of the vehicle. The blast damaged the windows of several dozen houses about 30 m away. The fire caused injuries to the two drivers. There was only about 40 m3 of gas in the trailer. If the incident would have happened when transport a full load, the consequences would have been worse.
Event Date
December 31, 1968
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was a traffic accident causing a roll-over of the trailer. The ROOT CAUSE had two components: a human error casuing the traffic incident and a lack of efficient protection of the pressure control system of the trailer, which was not designed for these of foreseeable impacts.