Skip to main content

Explosion in a refinery (978)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a refinery

The event occurred at a hydrogen tank (another source reports a 'conduit in an enclosed space') of a hydrogen generation unit of a refinery. The explosion caused a flare and a displacement of air that threw the contract workers against the refinery's metal structure. The workers were using an electric rotary sander on the inside the tank which had been had been drained three days before. The workers had already done previously the same work without incident.
Event Date
January 19, 2015
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was an explosion inside a hydrogen tank, which was still containing hydrogen despite workers were wroking in it. According to the sources, the possible causes could have been "inadequate maintenance, failure of following procedures, lack of work procedures or procedures". Additional job related causes could also have contributed, such as mental and physical stress due to long shift and tight deadlines. All these are plausible, however, absolutely no evidence is provided to support these theses. The ROOT CAUSES remain unknown.
Facility Information
Application Type
Application
hydrogen production unit, SMR
Specific Application Supply Chain Stage
Components Involved
hydrogen tank, pipe
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE FACILITY Acording to www. nsenergybusiness. com, tThe process units in the this refinery included an atmospheric distillation unit (ADU), a vacuum distillation unit (VDU), a catalytic cracking unit (CCU), a hydrodesulphurisation unit (HDS), a hydrotreating unit (DHTD), a hydrogen generation unit (HGU), a sulphur recovery unit (SRU), and a lubricant and paraffin plant. According to the Oil and Gas Journal, the hydrogen generation unit has a hydrogen generation capacity of 1. 1 million normal m3/day (approx. 100 kgH2/day). It produced high-purity hydrogen by SMR for for several downstream units within the refinery complex.
Operational Condition
Pre-event Summary
Maintenance works were ongoing.
Consequences
Number of Injured Persons
3
Number of Fatalities
0
Post-event Summary

The injuries were severe.

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Length (m)
1.00
References
References

REUTERS news of January 19, 2015 https://www. reuters. com/article/idUSL1N0UY0K720150119

HazardEx News https://www. hazardexonthenet. net/article/88918/Petrobras-refinery-explosion-seriously-injures-three-workers. aspx (Accessed December 2025)

The incident is also listed in P. Kannan, A web-based collection and analysis of process safety incidents Journal of Loss Prevention in the Process Industries 44 (2016) 171-192