Explosion in a hydrogen production unit
An explosion and fire occurred at a hydrogen production plant serving the hydrocracker and the diesel hydroteater of a nearby refinery. According to the plant owner, the incident occurred in the collection manifold, also referred to as a collection header or a transfer line, due to the failure of an external carbon steel pipe of the collection manifold. No injuries were reported among the employees and no damage to the nearby refinery, but exnsive damage to the hsyrogen production unit.
Event Date
December 8, 2009
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITATING CAUSE was the rupture of a carbon steel pipe, for undisclosed reasons. According to one of the sources, the plant owner and operator suited a contractor for the "for causing the energy release, saying they negligently failed to provide it with accurate safe operating temperatures, failed to warn of the potential for a cracked refractory inside the collection manifold and failed to design the collection manifold from materials able to withstand the potential operating temperature. " This statement suggests the failure of the pipe because experiencing to too high temperatures, due to (1) inadequate materials design, (2) deterioration of heat insulator. It also implies shortcoming I the communication between contractor responsible for the plant operation and its owner. The ROOT CAUSE could be a combination of shortcomings in design, inspection/maintenance/repair and eventually additional responsibility in the management of the plant.