Explosion in a hydrogen production unit (865)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a hydrogen production unit

An explosion and fire occurred at a hydrogen production plant serving the hydrocracker and the diesel hydroteater of a nearby refinery. According to the plant owner, the incident occurred in the collection manifold, also referred to as a collection header or a transfer line, due to the failure of an external carbon steel pipe of the collection manifold. No injuries were reported among the employees and no damage to the nearby refinery, but exnsive damage to the hsyrogen production unit.
Event Date
December 8, 2009
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITATING CAUSE was the rupture of a carbon steel pipe, for undisclosed reasons. According to one of the sources, the plant owner and operator suited a contractor for the "for causing the energy release, saying they negligently failed to provide it with accurate safe operating temperatures, failed to warn of the potential for a cracked refractory inside the collection manifold and failed to design the collection manifold from materials able to withstand the potential operating temperature. " This statement suggests the failure of the pipe because experiencing to too high temperatures, due to (1) inadequate materials design, (2) deterioration of heat insulator. It also implies shortcoming I the communication between contractor responsible for the plant operation and its owner. The ROOT CAUSE could be a combination of shortcomings in design, inspection/maintenance/repair and eventually additional responsibility in the management of the plant.
Facility Information
Application Type
Application
SMR
Specific Application Supply Chain Stage
Components Involved
unknown
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE FACILITY The hydrogen plant, which at the time of the incident had a capacity of 100 million standard cubic feet a day, was connected to a 300-mile hydrogen pipeline that runs along the Gulf Coast.
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Property Loss (offsite)

0

Post-event Summary

The vent caused damage to the manifold, a gas boiler, the facility's electrical system and other equipment near the manifold. The costs are unknown. No injuries were reported among the employees and no damage to the nearby refinery, but exnsive damage to the hsyrogen production unit.

Event Nature
Emergency Action
According to the spokeswoman, the fire was quickly under control.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Various news, such as: Reuter - https://www. reuters. com/article/business/energy/motiva-texas-hydrogen-unit-shut-after-blast-idUSN08206862/ Times Union - https://www. timesunion. com/news/article/praxair-hydrogen-plant-shut-after-explosion-280281. php (accessed September 2025)

Southeast Texas Records (notavailable anymore on line)