European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre
Explosion at the electrolysis unit of a chemical factory (778)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Explosion at the electrolysis unit of a chemical factory
An explosion occurred a the Lurgi electrolyser of a chemical factory. The plant suffered extensive damage and one man died. The investigation concluded that the explosion probably occurred on the oxygen separating drum into which hydrogen had leaked. After the accident the company carried out a mass balance on the hydrogen flows just prior to the explosion and found that no less than 50% was unaccounted for. The ingress of hydrogen into the oxygen drum was apparently due to corrosion/erosion in the electrolysis cells. The internal breakdown of the cells had probably been initiated some time before the accident. On April 2, a cracking noise was heard in the cell block, which may have indicated minor explosions. There was a system of monitoring the purity of the hydrogen and oxygen streams by hourly gas analyses performed by the process operator. The evidence suggested that these analyses were not always carried out and that assumed values were entered in the process log. One operator stated that he only did the analyses two or three times in every 12 h. The report on the accident by the HSE (1976b) estimated that on the basis of the explosion damage, the 1690 l oxygen drum contained a 13. 5% hydrogen, 86. 5% oxygen mixture, and the explosion produced a shock wave equivalent to 22 kg of TNT. It was calculated that this explosion would have caused an overpressure of 1. 03 kPa at 220 m and of 0. 21 kPa at 660 m on an open site. The factory was in an urban area with houses 180 m and a school 210 m from the electrolysis plant. Although on an open site some damage might be expected from an explosion of the size described at these distances, none actually occurred. Probably this was due to the fact that the electrolysis plant was housed in a building designed and constructed to direct any blast upward.
INITIATING cause is corrosion, hydrogen entered in an oxygen drum being part of an electrolytic process, causing an explosion. Root cause is related to lack of continuous gas quality control, which would have indicated presence of H2 on the O2 stream.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.