Explosion during transfer of hydrogen from a CGH2 trailer (590)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion during transfer of hydrogen from a CGH2 trailer

A series of explosions occurred on an industrial estate on a trailer containing 80,000 cubic feet of hydrogen. Hydrogen was being transferred from the trailer when it leaked, ignited and exploded. The trailer and adjacent buildings were set on fire and workshops severely damaged. Cars nearby were also set on fire.
Event Date
March 8, 1975
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE a leakage from the road tanker, during hdyrogen transfer, possibly caused by a mechanical failure and/or shortcoming in executing the transfer procedure. ROOT CAUSE It is impossible to attribute without doubt a root cause, but procedure, risk assessment and therefore management could be a good starting point.
Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved
trailer
Storage/Process Medium
Storage/Process Quantity
200
Location Type
Location description
Assuming that the value of 80,000. 00 cubic feet provided for the capacity represents standard cft of hydrogen, an inventory of ca. 200 kg was present.
Operational Condition
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Post-event Summary

The tanker and adjacent buildings were set on fire and workshops severely damaged. Cars nearby were also set on fire.

Lessons Learned
Flexible and/or mobile connections and systems are characterised by a higher probability of failure and gas leakage, than stationary systems. Great care should be put in considering this probability and its consequence, taking into account accidental scenarios also the environment in which the hydrogen transfer occurs. It is not only about the fire/explosion at the tanker, it is also about the domino effect which can be triggered by the standing by additional structures and machineries.
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Original source lost