An explosion and a fire in the hydrogen compression building (653)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

An explosion and a fire in the hydrogen compression building

Hydrogen leaked from a hydrogen compressor, ignited causing an explosion and a fire. The hydrogen fire further ignited roofing materials which had fallen down as the result of the explosion. The operator, who was outside the plant when the explosion occurred, pulled the emergency switch which shut down all the compressors. Although in a dazed condition he then checked in the motor room that all the motors had stopped. He was subsequently taken to hospital where he was found to have no physical injuries but was moderately shocked. The fire alarm was raised by the Gatekeeper who had heard the explosion and seen flames and smoke in the vicinity of the hydrogen plant. The works fire team were quickly on the scene but were advised not to extinguish the fire while hydrogen was still escaping, to prevent the likelihood of further explosion. The supply of hydrogen to the compression plant was cut off and the plant was electrically isolated before the arrival of the County Brigade. By the time they arrived, (within about seven minutes), the flow of hydrogen had stopped and the fire was quickly extinguished using water.
Event Date
May 22, 1971
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE of the first explosion was attributed to the failure of the coupling of a pressure gauge, the associated pipe and the related isolating valve. This conclusion was based on the finding of this component on the floor near a wall. The ROOT CAUSE is of difficult attribution. All similar couplings were found properly installed. A better risk assessment during intrinsic safe design could have recognised that failure of this type of coupling has worse consequences than other types of high pressure joints, and could have taken additional preventive measures.
Facility Information
Application Type
Application
hydrogen compression
Specific Application Supply Chain Stage
Components Involved
valve, compressor and motor
Location Type
Operational Condition
Pre-event Summary
The compressor involved had recently been overhauled and handed back to production on the day before the explosion. It ran satisfactorily for an hour before being shut down to fix clamps on the high pressure cooling coils which were vibrating. It was restarted on the following morning and again ran without signs of trouble until the explosion occurred after nearly an hours running.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Post-event Summary

The supply of hydrogen to the compression plant was cut off and the plant was electrically isolated before the arrival of the County Brigade. By the time they arrived, (within about seven minutes), the flow of hydrogen had stopped and the fire was quickly extinguished using water. Apart from the shocked operator, there were no other personnel injured. Damage due to the explosion, much of it superficial had been caused to the roof and walls of the building, plant instrumentation. and electrical wiring. Windows were broken in adjacent building. The fire caused only minor damage in the vicinity of the affected compressor.

Lessons Learned
The post-incident investigation attributed the initial loss of confinement to the failure of the coupling between the compressor and a pressure gauge system consisting of the gauge itself, the connecting pipe and the isolating valve. All similar couplings were checked and found to be satisfactory. Nevertheless, it was noted that the failure of this type of joint has more serious consequences than failures of other types of high pressure joint. The possibility of higher risks for critical joints should be recognised and taken into account during initial safe design.
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description extracted from the UK database ICHEME in PDF ICHEME database is no longer available for purchase, but data can be download as PDF for free. https://www. icheme. org/knowledge/safety-centre/resources/accident-data/ (accessed October 2020)