Skip to main content

Explosion and fire in a fertiliser production plant (949)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion and fire in a fertiliser production plant

A syngas leak (hydrogen + methane) occurred at exit of the ammonia production reactor and led to an explosion followed by a fire. The start point of the sequence of events was the syngas at the reactor outlet reaching an abnormal pressure of 150 bar and a temperature of 300°C. This caused a flange seal to move, causing the gases to leak. The accident caused a pressure waves and fire observed on the installations over a distance of 450 metres.
Event Date
July 24, 2010
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was an overpressure on a flange, causing its loss of confinement. The sources do not mention the reason(s) for the unexpectedly high-pressure value, but it could be assumed that it was an exceptional event, but not completely unexpected. From the corrective actions adopted it appears an absence of a risk assessment based on the possibility of ignition of flammable gases at the ammonia reactor, the usage of a inadequate components (flange) and the lack of effective communication of an alarm to personnel. These points hint at ROOT CAUSES related to inadequate (safety) design and risk management.
Facility Information
Application Type
Application
Fertilisers production
Specific Application Supply Chain Stage
Components Involved
ammonia reactor
Storage/Process Medium
Actual Pressure
15
Design Pressure
0
Location Type
Location description
DESCRIPTION OF THE COMPONENTS The pipe diameter at the exit of the ammonia reactor had a diameter of 300 mm (DN300). The flange used on this pipe was a model with a lenticular seal between the clamp and the tube, screwed to the flange by bolts.
Operational Condition
Consequences
Number of Injured Persons
5
Number of Fatalities
0
Currency
Property Loss (onsite)
12000000
Property Loss (offsite)

0

Post-event Summary

The accident caused 5 injuries. Material damage due to the pressure waves and fire was observed on the installations over a distance of 450 metres. The consequences for the site were estimated at €12,000,000.

Event Nature
Emergency Action
The plant and local firebrigades intervened, with a total of 28 men. They monitored air concentration of after-combustion gases During the mergency, the operator ensured the closing of all gas valves nad monitored reactor activities to prevent temperature changes of catalisator.
Release Type
Release Substance
syngas
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/50265/ (accessed October 2020)

Event description in the European database eMARS https://emars. jrc. ec. europa. eu/en/emars/accident/view/f8c4af35-d462-cb6e-1c6e-634009c396c9 (accessed October 2025)