Explosion and fire in a fertiliser production plant
A syngas leak (hydrogen + methane) occurred at exit of the ammonia production reactor and led to an explosion followed by a fire. The start point of the sequence of events was the syngas at the reactor outlet reaching an abnormal pressure of 150 bar and a temperature of 300°C. This caused a flange seal to move, causing the gases to leak. The accident caused a pressure waves and fire observed on the installations over a distance of 450 metres.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was an overpressure on a flange, causing its loss of confinement. The sources do not mention the reason(s) for the unexpectedly high-pressure value, but it could be assumed that it was an exceptional event, but not completely unexpected. From the corrective actions adopted it appears an absence of a risk assessment based on the possibility of ignition of flammable gases at the ammonia reactor, the usage of a inadequate components (flange) and the lack of effective communication of an alarm to personnel. These points hint at ROOT CAUSES related to inadequate (safety) design and risk management.