Explosion and fire of coke gas in a steel production plant (1030)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion and fire of coke gas in a steel production plant

An explosion followed by a fire occurred at a tar precipitator of gas treatment of a coke oven. The extractors were manually activated. Ten minutes later, the operator activates the internal emergency plan. The fuel supply to the installation was interrupted. Approximately two hours later the fire was extinguished by nitrogen purging. The operator estimated the maximum amount of material that reacted in the explosion of the tar precipitator at 170 kg in TNT equivalent. In total, the operator estimated that 36,790 t of coke oven gas were released and burned at the candles (torches above the oven batteries) and flares. The coke oven gas consisted mainly of hydrogen and methane. A crack had been identified in the steam circuit eight months before the accident, which could not be repaired without a precipitator shutdown. As the monitoring of the oxygen measurement at the precipitator outlet did not show any deviation, the repair was scheduled for the normal shutdown 3 days after the day of the accident. Several hypotheses as to the origin of the ignition energy were put forward: electrostatic due to the friction of the air/gas mixture (also composed of dust) on the metal plates, chemical due to the presence of pyrophoric materials or mechanical due to the fall of a metal part inside the precipitator. [ARIA event 56415]
Event Date
November 20, 2020
Record Quality Indicator
Region / Country
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The decision to continue operation after the detection of a crack in the steam circuit can be considered the root cause of this incident. The third-party expert report concluded that the most probable hypothesis was that the mixture of coke oven gases came into contact with the oxygen in the air coming from the leakage of the steam network, and ignited by the electrostatic energy generated by the friction of the gases on the metal walls. The explosion of an electrostatic tar precipitator had already occurred on this site in July 2005 and on other sites of the group abroad in November 2017 and in 2019. However, explosions have always occurred during the restarting of the precipitator by powering the electric fields, never during the washing and draining phases when the electric fields are not powered (no source of ignition). There was therefore no feedback and this risk had not been identified by the operator.
Facility Information
Application Type
Application
Steel manufacturing
Specific Application Supply Chain Stage
Components Involved
steel plant, tar precipitator, coke gases
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE PROCESS a tar precipitator is an electrostatic filter which collects dust and tar contained i the gas during the transformation of the coal in coke. The coke oven gas can then be used as energy source in other site processes.
Operational Condition
Pre-event Summary
At the moment of the incident, the precipitator was shutdown, being drained and washed.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

Y

Post-event Summary

The tar precipitation unit was destroyed. The estimated volume of coke oven gas burned at the candles and the flare was 3 776 600 Nm³. Flaring of the coke oven gas followed for 90 days until the tar precipitator was replaced. In total, the operator estimates that 36,790 t of coke oven gas were released and burned at the candles and flares. The operator carried out a health assessment and modelled the emission of SO2 which, was considered the only pollutant resulting from combustion which could have an impact on the population. They concluded that the daily average limit value for the protection of human health, the information and recommendation threshold and the alert threshold were not exceeded.

Event Nature
Emergency Action
16h15, Explosion followed by fire 16:25, the operator activated the internal emergency plan. The personnel is evacuated. A security perimeter is set up. The fuel supply to the installation is interrupted. 20:00, the fire was extinguished by nitrogen purging. The weakened structure was in danger of collapsing. At 8:30 pm, the upstream and downstream valves of the tar precipitator and scrubber were closed, coke oven gas was released, nitrogen was injected on the gas manifold and the structure was assessed. The operator installed solid gaskets on the flanges to isolate the tar precipitator units and the H2S scrubber. Flaring of the coke oven gas then followed for 90 days until the tar precipitator was replaced.
Release Type
Release Substance
Coke oven gas Mainly H2 CH4 CO CO2
Hydrogen Release Concentration (%)
0.00
Release Amount (kg)
36790.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

https://www. aria. developpement-durable. gouv. fr/fiche_detaillee/56415/

ARIA 56415 full report