Emergency stop of CHP plant

The incident occurred in a biogas-fed Solid Oxide Fuel Cell Stationary system, working in CHP mode. A sudden stop of the biogas feeding line caused the safety shutdown of the plant (SOFC module). The reason was ice formation inside the chiller (located after the biogas compressor) and inside the condensing discharge piping. This ice was creating a pressure drop across the compressor, which went into alarm mode. By the following maintenance, more heating power has been installed on the pipelines and the ventilation speed was reduced during winter time.
Event Date
December 17, 2017
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The ROOT CAUSE could be identified in a shortcoming of the design of the chiller.

Facility Information
Application Type
Application
CHP
Specific Application Supply Chain Stage
Components Involved
chiller, piping
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The event was unplanned. No signals or problems related to the biogas line were detected in the previous days
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

No consequences to people. No consequences to environment (no fuel release). The only damage is to the fuel cell plant since emergency shutdown can damage the cells. Zero maintenance costs, the compressor was under warranty period. Time Lost (hours): 1 month (because of Christmas break between the failure and the maintenance

Event Nature
Release Type
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Report provided but confidential