Dispenser nozzle freezing during hydrogen refuelling
This entry refer to a series of events occurred before the date given, which corresponds to the publication of the evidences at the Int. Conference on Hydrogen Safety 2015. The nozzle/receptacle connection froze when refuelling the on-board hydrogen storage system at the lowest precooling temperature of -40 C. However, freezing did not cause apparatus damage nor hydrogen leakage. The nozzle/receptacle is thus able to fuel safely even if the nozzle/receptacle is stuck due to ice.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The low temperature of the hydrogen caused the water vapour in the atmosphere to freeze around the nozzle-receptacle connection. Under specific environmental conditions creating high humidity, the quantity of ice forming does not allow for decoupling of the connection after the refuelling.