Detonation in a safety cabinet containing hydrogen cylinders
The safety cabinet with compressed hydrogen was located in a laboratory and used to supply hydrogen to an experimental facility. The safety cabinet was equipped with exhaust extraction. Due to a leak, technical assistance had been requested from the fire department. The head of laboratory shut off the electrical supply to the laboratory. Measurements showed that there was no potentially explosive atmosphere in the laboratory room. The plan of the fire department personnel was to open the door of the safety cabinet and close the valves of the gas cylinders While they were still putting on their protective equipment, the plant supervisor decided to purge the cabinet by blowing carbon dioxide into it from a fire extinguisher into the air intake aperture. It followed and immediate detonation then which destroyed the safety cabinet. [DECHEMA database event no. 2007/01] - date is also approximated because the DECHEMA database provide only the year of occurrence.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE of the hydrogen leak was a side connection on one of the gas cylinder valves, which had not been tightened sufficiently. Its seal had settled over the course of several days and was no more tight. The hydrogen started leaking into the cabinet out, forming a potentially explosive atmosphere despite the exhaust extraction inside the safety cabinet. The explosion was CAUSEd by the action of blowing in carbon dioxide. It CAUSEd an electrostatic charge which ignited the explosive atmosphere inside the cabinet.