Detection alarm in compressor room of a mobile production facility (1188)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Detection alarm in compressor room of a mobile production facility

This event with minor hydrogen releases occurred during the operation of a hydrogen compressor. The compressor was part of a mobile hydrogen production unit and connected to a bundle of cylinders with compressed hydrogen. The room gas detector sent a firstly a low-level alarm (alarm setting value = 4,800 ppm of hydrogen in air) and the equipment was temporarily shut down. To identify the location of the leak, the equipment was restarted and checked. 15 minutes later, the detector triggered a major alarm (alarm setting value = 9,600 ppm) and the equipment was shut down. A gas reaction was confirmed from the compressor. To identify the location of the leak, the upper, middle, and lower high-pressure compressor stages were disassembled and inspected. Two leak locations were found: (1) A penetration crack in the O-ring of the check valve on the discharge side of the left end cap of the high-pressure middle compressor. The two causes of this crack were a Blister phenomenon and a O-ring protrusion phenomenon due to deformation of the backup ring. (2). A scratch in the circumferential direction on the seat surface of the pipe joint (retainer) on the suction side of the left end cap of the high-pressure lower compressor. The cause of the circumferential scratch was a damage caused by partial contact of a part with a harder hardness than the seat surface when repeatedly connecting and disconnecting the fitting. [Note of HIAD validator: this event could be classified as near miss, if it were not for the bit unclear statement that a ‘reaction took place in the compressor’. It has now classified as a event with ignition, even if minor].

Event Date
February 25, 2019
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITATING CAUSE was two leaks on the compressor components. The ROOT CAUSE were probably to be attributed to material damage, possibly due to repeated use and/or installation mishaps.

Facility Information
Application Type
Application
compressor
Specific Application Supply Chain Stage
Components Involved

Fittings

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

0

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): https://www. khk. or. jp/public_information/incident_investigation/hpg_incident/incident_db. html (accessed May 2025)