Conventional fire on a CGH2 trailer (1142)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Conventional fire on a CGH2 trailer

A CGH2 tube trailer-tractor was travelling to deliver hydrogen to a customer, when a fire developed on right side of the tractor around the rear of the hood and passenger side door. Very quickly the entire power unit was engulfed in flames. The driver called 911. The highway was closed. Approximately 30 minutes later, the fire had spread to the tractor drive tires on the passenger side causing extreme heat on the bottom tubes of the trailer. Hydrogen began to leak and ignited. The fire continued to burn slowly until customer personnel lowered the pressure in the tube, which stopped the flow of gas and the fire self-extinguished. The burst disk did not appear to have failed. It was therefore presumed that the seal between the bull plug and the cylinder end melted and caused the leak. The units were released to a towing company approximately 7 hours later.

Event Date
November 14, 2013
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was a conventional fire from tractor components (similar incidents reported the brakes as the source of the over-heating). The ROOT CAUSE is unknown, because the result of the investigation is not available. However, the fact that the burst discs do not appear having failed indicates that the the pressure inside the tubes was not affected by the heat. It has been preliminary concluded that a component part of the pressure control system of the tube failed under fire, very likely the bull plug of the tubes. It indicate an inadequate safety design

Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved

seal

Storage/Process Medium
Storage/Process Quantity
322
Location Type
Location description

DESCRIPTION OF THE UNIT The trailer was carrying 10 tubes. On each tube end, a bull plug is installed, with an internal burst disk assembly screwed into it.

Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

148650

Property Loss (offsite)

0

Lessons Learned

The conventional brake fire which started this incident did not produce a heat input to the CGH2 tubes to cause their internal pressure to raise above the limit set by the pressure relief system. The burst disc did not open. The only damage caused by the fire was to a seal fitting, which caused a leak with limited consequences. Nevertheless, other cases started with conventional fires caused the venting of the whole hydrogen load, because the pressure relief valve were thermally or pressure-activated. Such a scenario has to be avoided when the trailers are in a confined space, such as a tunnel.

Event Nature
Emergency Action

The fire continued to burn slowly until customer personnel lowered the pressure in the tube, which stopped the flow of gas and the fire self-extinguished.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Incident I-2014020207 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal. phmsa. dot. gov/analytics/saw. dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)