Regarding cylinders, it is not necessary to capture the fuse-backed devices which are on the cylinder itself. However, all other relief devices and vent valves must exhaust from a vent system designed in accordance with CGA G-5.5. Also, note that NFPA 2-7.1.17 requires compliance with CGA G-5.5 regardless of storage quantity when the vent system is servicing pressure relief devices. Cylinders…

Category: System Design

Panel members have not encountered a device or area classification for ATEX approval within Canada. ATEX is a European Union directive and is not generally recognized within North American standards. The second link below references a UL similarity. https://news.nilfiskcfm.com/2017/03/atex-certification-applicable-north-america/;    https://www.ul.com/services/atex-certification…

Category: System Design

NFPA 2 has provisions for the use of LH2, and there are many existing fueling stations that store and use liquid hydrogen. One challenge for the use of LH2 in stations with small footprints is the code required separation distances from exposures. NPFA 2 has updated the separation distances with a risk informed approach in the 2023 edition.


Another possibility for public fuel…

Category: System Design

Liquid hydrogen is much less likely to pool than liquified natural gas (LNG) due to its low heat of vaporization. Very large facilities are often equipped with methods to enhance vaporization, such as crushed stone under tanks, as well as diversion systems to allow liquid hydrogen to spill and boil off in a safe area. Care needs to be taken that diversion systems do not create a hazardous…

Category: Storage

The design of vent systems is critical to the safety of the system. From a process perspective, the pipe design must be sufficient to withstand back pressure, internal pipeline pressure, deflagration pressure, thrust forces from the flow, and must be of a sufficient size to not create a restriction that prevents proper flow or activation of the devices. 

The vent system…

Category: System Design

It is best to avoid planned blowdown of large amounts of hydrogen inventory at high flowrates if possible.  Low flow releases from vent systems are normal and occur for purging, delivery operations, and maintenance activity.   A challenge with high flow blowdown of a hydrogen system is that venting large quantities of hydrogen can itself be a hazardous activity. …

Category: System Design

Welded systems are generally preferred, where possible, to reduce the likelihood of leaks.  Generally, even welded systems will need non-welded joints (e.g. unions, flanges, etc.) to allow maintenance replacement of components.  A low-pressure system would not be an exception to this preference.  However, piping at lower pressures and smaller sizes will…

Category: System Design

There are several concerns with “snuffing” a hydrogen fire from a vent stack. Most importantly, snuffing a hydrogen fire before the hydrogen is isolated can lead to the buildup of a hydrogen vapor cloud, which may then re-ignite, especially with hot surfaces available from the previous fire. The largest hazard is an explosion of the vapor cloud…

Category: System Design