Skip to main content

FAQ

There is no consensus on the “correct” answer. Small leaks of short duration have a much lower
probability of ignition compared to large releases. Ignition probability is affected by the operating
conditions, whether the release is from a leak or vent stack, and the surrounding environment. Since the
probability of ignition is high, hazard analyses will usually assume the hydrogen…

Static is a frequent source of ignition attributed to various hydrogen releases. Low levels of static
electricity are sufficient to ignite hydrogen – air mixtures. Static charges can be created by the
atmospheric disturbances and storms, high velocity particles entrained by the gas impacting stationary
objects, and human activity. Grounding of equipment and operators is important to…

Frequency and severity off consequences are situational and subject to the safety review team’s best judgement. One measure of severity is an estimate of the energy released if ignited. Assuming the worst-case mix to be stoichiometric, the energy content of a 500 mL of hydrogen in air is about 0.2 Wh (700 Joules), comparable to the energy release of a wooden, blue-tipped matchstick (~1kJ or 1…

Using tools inside a fume hood that may have a flammable gas mixture should be prohibited. A properly operating hood of the right capacity should keep the mixture of hydrogen in air inside the hood below the Lower Flammability Limit (LFL) of hydrogen further reducing any risk. 

If the use of tools is necessary, the source of hydrogen should be isolated before the work begins even if…

The key concern with any hydrogen release is the risk of creating a flammable mixture. There should be no environmental issues if you properly vent hydrogen to a safe area where it is diluted in air below the flammability limit before contacting an ignition source. Very small quantities of hydrogen are frequently releasing into a fume hood. Releases have to be small enough so that the vent air…

If the concentration of hydrogen is less than the Lower Flammability Limit (LFL) of 4% in an inert gas, it is unlikely that a leak of this gas mix will form a flammable mixture as it dilutes into air. For example, industry uses ‘forming gas’, a mixture of 4 to 5% H2 in nitrogen, as an oxide reducing agent in materials processing furnaces and soldering operations. This mixture can also be used…

Because hydrogen leaks frequently ignite, and because about half the time the ignition source is not identified, when evaluating hazards with hydrogen leaks, many people just assume the leak will be ignited. Note that consideration needs to be made for what may happen with immediate ignition (jet fire) and what may happen with delayed ignition (explosion). 

It is still important to…

Sprinkler systems and other fire suppression means are prescribed per building and fire codes to limit fire spread to other materials. In the case of a hydrogen leak and fire, it is best practice to isolate the hydrogen source, and let any residual hydrogen gas burn out. Even if the initial fire is extinguished, additional leaking hydrogen may accumulate and ignite with the potential for an…

Outside storage is generally considered safer and is required for large amounts of gas. Stationary storage should be located outside at a safe distance from structures and ventilation intakes, and protected from vehicle impact. 

Hydrogen storage separation distance requirements are typically based on the quantity and pressure of the hydrogen or the piping diameter, depending on the…

The answer is dependent upon the nature of the system and a hazard assessment which evaluates a balance of risk. 

Keeping the hydrogen in the vessel is better so the hydrogen release does not compound the original hazard. Large flowrates from vessels can create significant risk of vapor cloud explosion, jet explosion, or radiation exposure. Vent systems can also fail from poor…