Generally flaring is not recommended. Normally GH2 is not flared for most hydrogen equipment as the piping diameters are smaller. The largest stacks are the LH2 vent stacks on trailers and on tanks for the main safety valves are 3”. For GH2 systems the flare stacks are generally smaller in diameter. 

Flaring is a deliberate ignition of a hydrogen stream. If the hydrogen stream is to…

Category: System Design

There are several levels of documents which can be used to assist with the design, sizing, selection, and installation of the pressure relief device settings for LH2 tanks. 

Pressure vessel design codes, such as the ASME Boiler and Pressure Vessel Code will provide minimum requirements for design of pressure vessels (including LH2 tanks), relief devices, and relief systems. However,…

Safety codes globally have a requirement to provide a positive means to isolate energy sources and hazardous substances prior to performing maintenance. For gaseous hydrogen systems, methods such as a blind flange, a double block valve arrangement or a double block and bleed valve arrangement can provide that positive isolation.

Installing a blind flange requires breaking the supply line…

Keywords: Valves, Codes

Pressure relief systems may use reclosing devices like relief valves, non-reclosing devices like rupture discs, or a combination of both in parallel. Some systems may also be equipped with emergency blowdown systems that are operated by control systems. Selection of the proper devices is dependent on the system design and relative hazards. Variables that affect the selection include the type…

API 520, Sizing, Selection, and Installation of Pressure-relieving Devices Part I - Sizing and Selection, was written for use in the process industries in gas and liquid service.

CGA S1.3, Pressure Relief Device Standards-Part 3-Stationary Storage Containers for Compressed Gases was written for fixed equipment in gas service.

Which standard to use depends on the choice by the owner…

Equation 6.3.1.1 in CGA S1.3 is based on modeling to API methods described in: Heitner, T. Trautmauis, and M. Morrissey, “Relieving Requirements for Gas Filled Vessels Exposed to Fire,” 1983 Proceedings-Refining Department, Volume 62, American Petroleum Institute, Washington, D.C., pp. 112-122.

This method considers the transient nature of the vessel warming in combination with the…

Fuels like gasoline are exempt from OSHA process safety management (PSM) requirements. When asked about the applicability for hydrogen storage larger than 10,000 lb (4500 kg) being used as a fuel, OSHA responded with an interpretation that can be found at https://www.osha.gov/laws-regs/standardinterpretations…

NFPA 2 Annex G provides a summary of the conflicts with 29 CFR 1910.103. This is language that has been in NFPA 55 for several cycles as this conflict has existed for many years. The requirements in the Federal Regulations were established in the early 1970s. Since that time, OSHA has not had sufficient resources to update the applicable provisions.

The primary difference between OSHA…

Category: System Design

The recognized and generally accepted good engineering practices (RAGAGEP) for employing a nitrogen purge into a hydrogen vent stack is that inerting is not generally used for nitrogen purge in a hydrogen vent stack because most inert gases freeze at liquid hydrogen temperatures. The vent stack should be designed for a fire and the internal overpressure caused by a deflagration. If inerting is…

Category: System Design

The recognized and generally accepted good engineering practices (RAGAGEP) for employing a purge into a hydrogen vent stack is that inerting is not generally used. Best practice is that the vent stack should be designed for a fire and the overpressure caused by an internal deflagration. This is typically not an issue for smaller sizes (less than 4”) and when using typical materials for a vent…

Category: System Design