There are dozens of safety considerations for safe design of hydrogen vent stacks. Their primary function
is to vent the hydrogen safely, so vent stacks should be designed such that the gas dispersion and
radiation profile (if ignited) do not impact surrounding equipment, buildings, or people. Documents such
as CGA G5.5, Hydrogen Vent Systems, provide numerous details regarding design…

Category: System Design

Electrolyzers should be installed per manufacturer recommendations and meet the criteria of their
listing, such as ISO 22734, Hydrogen generators using water electrolysis - Industrial, commercial, and
residential applications. There are several methods such as partitions, enclosures, ventilation, and
purging that can be used to address non-classified electrical equipment.

Category: System Design

Flare-less compression style fittings are commonly used. Choose tubing materials and tube wall thicknesses suitable for hydrogen and pressures you are using. Make sure all tubing joints are properly made, mechanically supported to minimize stress and vibration, are in a ventilated space, and are easily accessible for inspection and leak testing. 

Category: Miscellaneous
Keywords: Tubing, Guidelines

See H2Tools, Best Practices: Purging, for a description of different purging approaches for hydrogen systems.

Category: System Design

There are several resources that can help review designs, such as the Hydrogen Safety Panel and other outside consultants that are members of the Center for Hydrogen Safety.

Category: System Design

In general, indoor storage should be limited and the use of hydrogen indoors should be the least necessary. Look to store flammable gases outdoors in dedicated protected area when practicable. Check to see what adopted building and fire codes in your jurisdiction say. NFPA 2, Hydrogen Technology Code, Sections 6.4.1 and 16.3 prescribe requirements to limit hydrogen storage and use in…

Category: Miscellaneous

In laboratories, 316 stainless steel tubing is frequently the first choice for small flow and pressures less than 2800 psi (19 MPa). See Best Practices: Material Compatibility for hydrogen compatibility with various materials. Always work within manufacturer’s pressure ratings adjusted for temperature. Read and follow…

Category: System Design

Rupture discs open very rapidly. Historically, rupture discs opening at high pressure (1000 psig and above) have caused the most damage due to deflagration/detonation. Timing a rupture disc would not be possible. Additionally, how would you have a pilot light on a moving tube trailer? Even with a pilot light at the end of the stack may blow out due to the initial high velocity.

See…

Category: System Design

Vent stacks must be designed for a fire at the outlet. The mesh is designed to ensure no blockage of the vent stack by animals/insects. 

Additionally, the mesh must be designed for pressure drop to ensure code-compliant back pressure on the relief devices.

Category: System Design

Yes, numerous incidents have occurred where frozen air (which contains oxygen) has built up within a hydrogen process or vent system. These incidents with vent systems incorporate more than just a vent stack, but include a vent system consisting of additional atmospheric equipment (such as a tank) where the equipment stays cold and allows air into the system in contact with a cold hydrogen…

Category: System Design