The recognized and generally accepted good engineering practices (RAGAGEP) for employing a purge into a hydrogen vent stack is that inerting is not generally used. Best practice is that the vent stack should be designed for a fire and the overpressure caused by an internal deflagration. This is typically not an issue for smaller sizes (less than 4”) and when using typical materials for a vent…

Category: System Design

In the U.S., there is no specific national requirement for fuel cell test equipment to be certified. There may be requirements from the local authority having jurisdiction (AHJ). Local building codes will likely point to compliance with NFPA 2/55 for the hydrogen and other gas supply systems, ASME Boiler and Pressure Vessel Code for vessels, ASME B31 piping codes for piping, and National…

Category: Miscellaneous

The answers are in context of PEM and alkaline electrolysis operating at or below 30 bar and below 85 deg C°. A general suggestion: Ask component suppliers about material compatibility, but do an independent investigation to confirm. As a general resource,  safety data sheets (SDSs) sometimes provide material compatibility information. Specific recommendations follow. 

    …
Category: System Design

It depends on the facility and risk assessment, but generally multiple pressure and temperatures to one vent stack is not the best practice unless all are similar in pressure and temperature, and the streams have compatible composition and flow rate. Care must also be taken to prevent reverse flow and misdirected flow between portions of the system. Additionally, one vent stack can become a…

Category: System Design

Requirements for local jurisdictions vary, so the AHJ should be consulted, but NFPA 2:2023, Hydrogen Technologies Code, Chapter 13 has requirements for installation of hydrogen generators up to 100 kg H2/h. Section 13.3.1 General says permitted water electrolysis systems are to be listed to ISO 22734:2019, Hydrogen Generators Using Water Electrolysis - Industrial, Commercial, and Residential…

Category: System Design

Cylinders are required to be tested periodically to verify structural integrity. The most common test method is hydrotesting, which means water is the most likely impurity that solidified in the inlets. Drying the tanks is normally a requirement after performing a hydrotest. In the USA, CFR 49 CFR § 180.209 applies: https://www.law…

The end use of hydrogen usually drives the cleaning for initial construction. 

  1. When the hydrogen is used for combustion and many industrial applications, normal care during construction and leak testing is usually adequate.
  2. When the hydrogen needs to be very pure, as is the case for PEM fuel cell applications, more…
Category: System Design
Keywords: Clean, Component, System

Because hydrogen is labeled as a hazardous substance, sometimes people are concerned about the environmental impact of releasing liquid hydrogen. There are currently no regulations that require reporting of hydrogen releases for environmental reasons.


However, there are safety implications. For example, the US DOT requires reporting of hazardous materials releases under certain…

Category: Miscellaneous
Keywords: Liquid, Spill, Ditch, Sewer, Lake, River

Purging of vent systems is not required and in most instances is not recommended.

A nitrogen purge is generally not needed for a vent system designed in accordance with CGA G-5.5.  However, there are times where this might be considered or required due to the specific design of a system.  Where determined by a risk review to be needed, A continuous purge into a vent system…

Category: Miscellaneous

Catalytic recombiners are effective at preventing flammable hydrogen mixtures and also sometimes useful to monitor hydrogen concentrations through heat evolution when an oxidizer is present. Careful considerations must be made when integrating these elements into a design, so that they do not become a source ignition (and/or flame arrestors prevent propagation of a flame front) and the…

Category: System Design