It is common to have combustible materials and fuels in a building during construction activities. Commissioning is typically considered part of construction. It is good to see that fire suppression is available. However, given the lack of alarm capabilities, it would seem prudent to have a fire watch posted when hazardous materials are present or being used. Regarding requirements, the…
The HSP recommends against the use of glycols for pressure tests due to the difficulty of adequately removing all glycol that might be left in a system after a hydrotest. The HSP recommends a pneumatic test at 110% of the system maximum allowable working pressure (MAWP), which is acceptable by code. Due to an increased danger with pneumatics vs hydrotesting, establish a pressure test zone for…
The Panel recommends performing a pressure test at 110% of design pressure. This requirement should be applied to all systems regardless of construction type since the intent is to ensure pressure integrity and proper installation. All fitting types have modes of failure during installation. For example, there are numerous examples where compression fittings have had ferrules installed…