Skip to main content

FAQ

Liquid hydrogen is rarely vented as a liquid. If liquid hydrogen is vented, there should be a means to ensure that it is fully vaporized. The vent systems for LH2 tanks are connected to the vapor space on the tanks to ensure in most instances, this occurs. Most vents from a liquid hydrogen system will vent gaseous hydrogen, but this gas, may still be as cold as -420 F. There are no code…

Category: Miscellaneous

At least three of the ASME B31 piping codes are logical choices:

  • ASME B31.1, Power Piping
  • ASME B31.3, Process Piping
  • ASME B31.12 Hydrogen Piping and Pipelines

Considerations for code selection include:

  • Requirements imposed by the authority having jurisdiction, whether by direct reference or…
Category: Piping

The requirements of the code used for the original construction apply. The piping may meet the requirements of more than one code. In which case, the code used for changing the rating may be different than the original code of construction. In any case, the re-rated system should meet all of the requirements of the selected code. Note that if the original proof test of the system was…

Category: Piping

The code used for repair and alterations of an existing system depends on the code used for construction as well as on the requirements imposed by the jurisdiction. Note that getting a permit from the jurisdiction may be necessary for an extensive alteration.

Code of ConstructionGenerally Accepted Code for Repair and Alterations…
Category: Piping
Keywords: Piping, Codes

It depends on the construction and location of the lights. Assuming the typical practice of using non-classified lighting on vehicles, operation of those lights during a delivery could provide an ignition source if located within the classified area near the delivery or venting activity. A more modern LED lighting systems may present a lower risk.

Category: Miscellaneous

Because a small spark can ignite hydrogen-air mixtures, precautions such as using spark-resistant tools is one method that can be considered to reduce the probability of an ignition. However, there is little evidence that spark-resistant tools make a significant difference.   


Spark-resistant tools are made of nonferrous materials that are inherently weaker than the steels…

Category: Miscellaneous

In the U.S., there is no specific national requirement for fuel cell test equipment to be certified. There may be requirements from the local authority having jurisdiction (AHJ). Local building codes will likely point to compliance with NFPA 2/55 for the hydrogen and other gas supply systems, ASME Boiler and Pressure Vessel Code for vessels, ASME B31 piping codes for piping, and National…

Category: Miscellaneous

Because hydrogen is labeled as a hazardous substance, sometimes people are concerned about the environmental impact of releasing liquid hydrogen. There are currently no regulations that require reporting of hydrogen releases for environmental reasons.


However, there are safety implications. For example, the US DOT requires reporting of hazardous materials releases under certain…

Category: Miscellaneous
Keywords: Liquid, Spill, Ditch, Sewer, Lake, River

Purging of vent systems is not required and in most instances is not recommended.

A nitrogen purge is generally not needed for a vent system designed in accordance with CGA G-5.5.  However, there are times where this might be considered or required due to the specific design of a system.  Where determined by a risk review to be needed, A continuous purge into a vent system…

Category: Miscellaneous

Off gassing of hydrogen from battery sources depends on battery chemistry, usage/duty cycle, age, and other considerations. The specific battery manufacturer should provide recommendations for fire prevention and mitigation in battery charging rooms as the battery itself impacts how an event would be mitigated. Adequate ventilation such that combustible mixtures cannot develop is a general…

Category: Miscellaneous