NFPA 2 has provisions for the use of LH2, and there are many existing fueling stations that store and use liquid hydrogen. One challenge for the use of LH2 in stations with small footprints is the code required separation distances from exposures. NPFA 2 has updated the separation distances with a risk informed approach in the 2023 edition.


Another possibility for public fuel…

Category: System Design

If liquid hydrogen usage is sufficiently high at the fueling station, there may be no need to vent any boiloff generated from the LH2 storage tank. Boil-off gas should be minimized through system design, but where needed, the boil-off hydrogen along with any other hydrogen released must be vented through a local vent stack which is constructed to safely vent the hydrogen in accordance with CGA…

The design of vent systems is critical to the safety of the system. From a process perspective, the pipe design must be sufficient to withstand back pressure, internal pipeline pressure, deflagration pressure, thrust forces from the flow, and must be of a sufficient size to not create a restriction that prevents proper flow or activation of the devices. 

The vent system…

Category: System Design

It is best to avoid planned blowdown of large amounts of hydrogen inventory at high flowrates if possible.  Low flow releases from vent systems are normal and occur for purging, delivery operations, and maintenance activity.   A challenge with high flow blowdown of a hydrogen system is that venting large quantities of hydrogen can itself be a hazardous activity. …

Category: System Design

Welded systems are generally preferred, where possible, to reduce the likelihood of leaks.  Generally, even welded systems will need non-welded joints (e.g. unions, flanges, etc.) to allow maintenance replacement of components.  A low-pressure system would not be an exception to this preference.  However, piping at lower pressures and smaller sizes will…

Category: System Design

There are several concerns with “snuffing” a hydrogen fire from a vent stack. Most importantly, snuffing a hydrogen fire before the hydrogen is isolated can lead to the buildup of a hydrogen vapor cloud, which may then re-ignite, especially with hot surfaces available from the previous fire. The largest hazard is an explosion of the vapor cloud…

Category: System Design

The lifetimes of these components will vary depending upon the application, their installation environment, and usage. It is also important to adhere to the component inspection, maintenance and replacement specifications as recommended by the manufacturer. However, as many are made of stainless steel, their life expectancy is longer than other materials. Estimated lifetimes are below in years…

Category: System Design

In the U.S., liquid hydrogen fueling stations and dispensing equipment are addressed within NFPA 2, Chapter 11. Dispensing is covered within Section 11.3. When liquefied hydrogen is used as the supply for high pressure gaseous fueling, then Chapter 10 of NFPA 2 would apply.
ISO standards are also being developed for global LH2 fueling protocols.