A pressure of 600 kPa (87 psi) is relatively moderate, so the combustion properties are similar to those at atmospheric pressure where the autoignition temperature of hydrogen is 585°C. 

Category: Properties

H2-air flammability limits vary with temperature  . The H2-air lower flammability limit is virtually the same as the H2-O2 lower limit. However, the H2-O2 upper flammability limit increases substantially to about 95% at room temperature and gets even higher at elevated temperatures.

…
Category: Properties

In the U.S., liquid hydrogen fueling stations and dispensing equipment are addressed within NFPA 2, Chapter 11. Dispensing is covered within Section 11.3. When liquefied hydrogen is used as the supply for high pressure gaseous fueling, then Chapter 10 of NFPA 2 would apply.
ISO standards are also being developed for global LH2 fueling protocols.
 

Most common odorants will contaminate fuel cells. Additionally, hydrogen's small molecule and high buoyancy make it challenging to find a compatible odorant. Research is being conducted on fuel cell compatible odorants, but there are none currently in use. Like liquefied natural gas, liquid hydrogen also can’t be odorized due to its cryogenic temperature.

Category: Properties
Keywords: Odorant, Odor

Hydrogen flames can be nearly invisible in daylight, especially at low flowrates. The concentration of hydrogen does not have much effect on the color of the flame. Many hydrogen incidents or fires will have a bright orange hue, or even yellow flames. The color is primarily caused by contaminants that is either naturally in the air in certain environments, swept into the air during the release…

Category: Properties
Keywords: Fire, Flame

Yes, small flowrate vents may be invisible, particularly in daylight. Sometimes it may still be possible to see heat striations in the air from the heat generated by the fire, but it can be difficult to discern at low flowrates. 

Category: Properties
Keywords: Vent, Flame, Flow

The “Hydrogen Ready Appliances Assessment Report” published by the Northwest Energy Efficiency Alliance (NEEA) in February, 2023, is one of the most recent studies on this topic.  Several key items from the report pertaining to this question include the following:

1.    “There appears to be growing consensus that blends of up to 20% or perhaps even 30% are…

Category: Properties

Many methods are used to mitigate the risk of a tube trailer hose loss of containment incident. Examples that otherwise exceed code requirements are provided below. These have been deployed in various combinations depending on the risk analysis for a particular system: 

  1. Installation of automatic shutoff valves on the tube trailer upstream of the hose to activate upon hose…

A "drop and swap" delivery system using tube trailers is a common and accepted method of supply for both industrial and fueling station applications. While NFPA 2 - 2023, paragraph 10.6.3.5 states, "The use of hose in a hydrogen dispensing system shall be limited to vehicle fueling hose," this is intended for the dispenser itself, not the entire fueling station. This does not limit the use of…

A design condition for vent stacks is to always assume that the hydrogen will ignite. The stack musts be designed such that it can withstand those conditions as well as minimize radiation to surrounding personnel and exposures. Although hydrogen fires have comparatively low radiation compared to hydrocarbon fuels, the radiation from large releases from vent stacks can be quite high. Documents…

Category: Properties