After moving people to a safe location, if it safe to do so, isolate the source of hydrogen feeding the fire. Burns and explosions are hazards when exposed to a hydrogen fire. For more best laboratory preventative safety practices as well as first responder response to a hydrogen incident See both CHS training resources: 

  • …

The Panel considers two approaches to be acceptable. 

  1. Stainless steel (corrosion resistant) lines embedded in concrete. This keeps the piping out of direct contact with the earth and provides a degree of physical protection from activities such as digging.
  2. Lines…
Category: Piping

The HSP is not familiar with this particular fitting or its potential application in H2 service but can offer engineering judgment. Many similar compression-type swaged fittings are used in H2 service. These fittings must be used within the manufacturer recommendations for pressure, temperature, and fluid service. Deformation is also introduced into stainless steel tubing in other ways, such…

Category: Piping

I am communicating with a company that is exploring this technology for an application involving a mixture of flammable gases, including hydrogen.

Category: Explosions

There is limited published research on the effect of water sprays on hydrogen deflagrations and deflagration-to-detonation transition, and more extensive data on water spray effects on hydrocarbon gas explosions. The results show the benefits, where there are benefits, to be highly scenario dependent. For example, Carlson et al. (Atomics International report, 1973) described hydrogen…

Category: Explosions

The lesson learned (LL) article referenced in the question cites an incident that occurred in December 1969. While there may have been other accidents, the HSP does not have any other LL articles on alkaline water electrolysis explosions. In the LL article that was updated in 2017, the technology described employs a potassium hydroxide (KOH) electrolyte solution. The KOH electrolyte is held by…

Category: Explosions

No, but it is always necessary to determine the possibility of an adverse chemical reaction with the particular material being used for the mesh.

Category: Explosions

The Panel has not received such inquiries. Section 14.2 of NFPA 69 Standard for Explosion Prevention Systems covers foam and mesh requirements. NFPA 69 states in 14.3.4 that the tests shall be conducted with a flammable gas/air mixture with a fundamental burning velocity representative of the burning velocities of flammable vapors expected in the intended applications.

Category: Explosions

Explosion testing with hydrogen should be utilized only where there is not an established alternative and then only by personnel experienced in such testing. 
Testing with hydrogen is always a challenge and needs to be approached carefully due to significant differences in properties between hydrogen and propane. Hydrogen can develop significantly higher overpressures and preliminary…

Category: Explosions