Hydrogen gas storage and fuel cell systems are typically closed systems with a variety of monitoring and control functions to prevent leaks. Please check with the bus manufacturer and authority having jurisdiction to verify this is acceptable per their direction. However, a good safety practice would be to minimize the time spent indoors for these activities. Hydrogen vehicles maintained in a…

Training personnel and equipping them with portable gas detectors to properly identify the gas that is
leaking can play an important role in both troubleshooting and emergency response.

Category: Detectors

Researchers from Sandia National Laboratories have conducted extensive research on these topics. They have reviewed the current literature, identified knowledge gaps in alternate fuel vehicles and tunnel safety, and developed a generalizable framework to assess tunnel safety for a diverse range of alternate fuel vehicles. Supported by US Department of Energy (DOE) and Federal Highway…

Keywords: FC Vehicles, Safety

It’s not clear if “mobile” in the question refers to vehicle fuel tanks, or vessels used for transportation of hazardous materials.

  1. If it’s a Type 4 vessel for transportation of hazardous materials, it will be built to a special permit that details the inspection requirements. Special permits vary but they are generally…

FCEVs usually contain only a minimal amount of hydrogen fuel pressure (several Mpa) to support getting the car on and off car carriers. Panel members are not aware of any hydrogen release incidents during vehicle loading and don’t know what the probability of such a leak is considering the loading operations. A risk assessment accounting for the probability of collisions as well as leaks from…

I am communicating with a company that is exploring this technology for an application involving a mixture of flammable gases, including hydrogen.

Category: Explosions

Generally speaking, the International Fire Code and NFPA 2 apply to non-transportation use of hydrogen. These are maturing quickly, with NFPA 2 currently having issued its most recent edition in 2023. Standards for both on-board LH2 tanks and LH2 tankers for bulk fuel transport are managed by the U.S. Department of Transportation (DOT) and are well established. DOT transport requirements for…

There is limited published research on the effect of water sprays on hydrogen deflagrations and deflagration-to-detonation transition, and more extensive data on water spray effects on hydrocarbon gas explosions. The results show the benefits, where there are benefits, to be highly scenario dependent. For example, Carlson et al. (Atomics International report, 1973) described hydrogen…

Category: Explosions

The lesson learned (LL) article referenced in the question cites an incident that occurred in December 1969. While there may have been other accidents, the HSP does not have any other LL articles on alkaline water electrolysis explosions. In the LL article that was updated in 2017, the technology described employs a potassium hydroxide (KOH) electrolyte solution. The KOH electrolyte is held by…

Category: Explosions

No, but it is always necessary to determine the possibility of an adverse chemical reaction with the particular material being used for the mesh.

Category: Explosions